Home › Plant › Energy supply › Ozonisation -Offline-
Ozonisation -Offline-
| Ozonisation Plant for Water PreparationComplete Ozonisation Plant for Water Preparation in very good condition, build in 1993.Plant is dismantled and packed |
 |
| Ozonisation Plant |
10 m3ph
|
1993
|
Chriwa
|
| Conditioning- depending from raw water- achieved values in operation: |
Fe: < 0,10 mgplMn: < 0,05 mgplNO2: < 0,02 mgpl
|
-
|
-
|
| Plant Overview |
Raw Water SupplyAtomisationtowerOzonreaktor
HighPerformancefilter
Activated Carbon Filter
Polisher
|
-
|
-
|
| Ozonisation Plant - technical Details |
| |
Capacity |
10 m3ph |
- |
- |
| |
Pressure Raw Water |
max. 3 bar |
- |
- |
| |
Temperature Raw Water |
max. 40° C |
- |
- |
| |
Connection Raw Water |
DN50, PN10 |
- |
- |
| |
Plant Pressure |
p = 3 bar (ü) |
- |
- |
| |
Power Supply |
220/660 V, 50 Hz |
- |
- |
| |
Total-kW-requirement |
ca. 16 kW |
- |
- |
| |
Room height |
ca. 6.000 mm |
- |
- |
| |
Space requirements |
ca. 30 m2 |
- |
- |
 |
| High Performance Filter - technical Details |
| Pressure |
3 bar |
- |
- |
| Scavening Air |
75 m3ph |
- |
- |
| Scavening Water |
30 m³ph |
- |
- |
| Re-Scavening Air |
6…8 min |
- |
- |
| Re-Scavening Water |
6…8 min |
- |
- |
| Filter resistance |
max. 2,5 mWS |
- |
- |
  |
| Activated Carbon Filter - technical Details |
| Pressure |
max. 4 bar
|
-
|
-
|
| Temperature |
max. 40 ° C
|
-
|
-
|
| Sterilisation Temperature |
85°…90° Cmax. 110° C
|
-
|
-
|
| Pressure Sterilisation |
max. 0,5 bar
|
-
|
-
|
| Rinsing Water 1 |
30 m3ph
|
-
|
-
|
| Rinsing Time |
8 min
|
-
|
-
|
| Rinsing Water 2 |
4 m3ph
|
-
|
-
|
| Rinsing Time |
25 min
|
-
|
-
|
| Filter resistance |
max. 0,6 bar
|
-
|
-
|
| Filter resistance increase |
max. 2…3 mWS
|
-
|
-
|
| Rinsing frequency |
1…2 times pweek
|
-
|
-
|
| Sterilisation |
on demand
|
-
|
-
|
| Warum-up time |
1…1,5 h
|
-
|
-
|
| Cooling-off time |
60 min (minimum)
|
-
|
-
|
 |
| Polisher - technical Details |
| Pressure |
max. 6 bar
|
-
|
-
|
| Material |
1.4571
|
-
|
-
|
| Quantity of Filtercandles |
5
|
-
|
-
|
| Length of Candles |
30 Zoll
|
-
|
-
|
| Connections |
DN50 (2 Zoll)
|
-
|
-
|
| Connections |
DIN 11851
|
-
|
-
|
 |